  1.     SECTION 07223
  2.  
  3.     METAL BUILDING ROOF INSULATION
  4. NOTE ** Therm-All, Inc. ConSealTab insulation system.
  5. NOTE ** 
  6. NOTE ** This section is based on products manufactured by Therm-All, Inc., which is located at the following address:
  7. NOTE **     31387 Industrial Parkway
  8. NOTE **     North Olmsted OH 44070
  9. NOTE **     Tel:  (888) 2INSUL8
  10. NOTE **     Fax:  (216) 734-5282
  11. NOTE ** 
  12. NOTE ** Therm-All, Inc. offers a complete line of insulation products, including the ConSealTab system specified in this section.
  13. NOTE ** 
  14. NOTE ** SECTION 07223 - METAL BUILDING ROOF INSULATION, Copyright 1997, The Architect's Catalog, Inc.
  15.  
  16.  
  17. PART 1    GENERAL
  18.  
  19. 1.1    SECTION INCLUDES
  20. NOTE ** Delete items below not required for project.
  21.  
  22.     A.    Insulation Batts.
  23.  
  24.     B.    Thermal Blocking.
  25.  
  26. 1.2    RELATED SECTIONS
  27. NOTE ** Delete any sections below not relevant to this project; add others as required.
  28.  
  29.     A.    Section 07220 - Roof and Deck Insulation.
  30.  
  31.     B.    Section 13120 - Metal Building Systems.
  32.  
  33. 1.3    REFERENCES
  34. NOTE ** Delete references from the list below that are not actually required by the text of the edited section.
  35.  
  36.     A.    ASTM C 236 - Standard Test Method for Steady-State Thermal Performance of Building Assemblies by Means of a Guarded Hot Box.
  37.  
  38.     B.    ASTM C 553 - Standard Specification for Mineral Fiber Blanket and Thermal Insulation for Commercial and Industrial Applications.
  39.  
  40.     C.    ASTM C 578 - Standard Specification for Preformed, Cellular Polystyrene Thermal Insulation.
  41.  
  42.     D.    ASTM E 84 - Standard Test Method for Surface Burning Characteristics of Building Materials.
  43.  
  44.     E.    ASTM E 96 - Standard Test Methods for Water Vapor Transmission of Materials.
  45.  
  46.     F.    FS HH-I-558B - Insulation, Blocks, Boards, Blankets, Felts, Sleeving, (Pipe and Tube Covering), and Pipe Fitting Covering, Thermal (Mineral Fiber, Industrial Type).
  47.  
  48. 1.4    SYSTEM DESCRIPTION
  49. NOTE ** Retain one or more of the following paragraphs specifying performance requirements for insulating assemblies.
  50.  
  51.     A.    Minimum tested thermal transmittance of insulating assembly for nominal R-13 material, in accordance with ASTM C 236:  R-value 9.91 (1.61 metric equivalent); U-value 0.101 (0.573 metric equivalent).
  52.  
  53.     B.    Minimum tested thermal transmittance of insulating assembly for nominal R-13 material with thermal blocking, in accordance with ASTM C 236:  R-value 10.57 (1.86 metric equivalent); U-value 0.095 (0.539 metric equivalent).
  54.  
  55.     C.    Minimum tested thermal transmittance of insulating assembly for nominal R-19 material, in accordance with ASTM C 236:  R-value 12.08 (2.12 metric equivalent); U-value 0.083 (0.471 metric equivalent).
  56.  
  57.     D.    Minimum tested thermal transmittance of insulating assembly for nominal R-19 material with thermal blocking, in accordance with ASTM C 236:  R-value 16.08 (2.83 metric equivalent); U-value 0.062 (0.352 metric equivalent).
  58.  
  59. 1.5    SUBMITTALS
  60.  
  61.     A.    Submit under provisions of Section 01300.
  62.  
  63.     B.    Product Data:  Manufacturer's descriptive literature for insulation batts.
  64.  
  65.     C.    Verification Samples:  Two (2) lengths of insulation batt, of specified thickness, minimum length 2 feet (609 mm).
  66.  
  67.     D.    Quality Assurance Submittals:
  68.         1.    Test reports:  Certified reports from independent testing laboratory supporting compliance of insulating assembly to specified requirements.
  69.         2.    Manufacturer's instructions:  Printed installation instructions, including product storage requirements.
  70.  
  71. 1.6    DELIVERY, STORAGE, AND HANDLING
  72.  
  73.     A.    Store products of this section in manufacturer's unopened packaging until installation.
  74.  
  75.     B.    Maintain storage area conditions for products of this section in accordance with manufacturer's instructions until installation.
  76.  
  77. 1.7    PROJECT CONDITIONS
  78.  
  79.     A.    Specified product requires right to left installation; examine project conditions, and order opposite side rolls for left to right installations.
  80.  
  81.  
  82. PART 2    PRODUCTS
  83.  
  84. 2.1    MANUFACTURERS
  85.  
  86.     A.    Acceptable Manufacturer:  Therm-All, Inc.; 31387 Industrial Parkway, North Olmsted OH 44070; ASD. Tel:  (888) 2INSUL8, Fax:  (216) 734-5282.
  87. NOTE ** Delete one of the two following paragraphs; coordinate with Division 1 requirements.
  88.  
  89.     B.    Requests for substitution will be considered in accordance with provisions of Section 01600.
  90.  
  91.     C.    Substitutions:  Not permitted.
  92.  
  93. 2.2    MATERIALS
  94.  
  95.     A.    Insulation Batts:
  96.         1.    Acceptable product:  Therm-All ConSealTab.
  97.         2.    Batt:  Glass-fiber batt insulation conforming to ASTM C 553 and FS HH-I-558B, and bearing approval stamp of the following:
  98.             a.    NAIMA 202-96 (North American Insulation Manufacturers Association).
  99.             b.    NIA 404 (National Insulation Association).
  100. NOTE ** The manufacturer recommends the following facing type as minimum acceptable for most building applications; other facing are available, ranging from premium quality to economy.  Consult with manufacturer for options, and review performance characteristics for other facings.
  101.         3.    Facing:  White polypropylene scrim kraft, standard duty metallized, adhered to one face of batt to form nominal 6 inches (152 mm) wide continuous exposed tab along one long edge, and nominal 6 inches (152 mm) wide continuous non-adhered flap along other long edge.
  102.         4.    Flame spread rating, in accordance with ASTM E 84:  25, maximum.
  103.         5.    Water vapor transmission, in accordance with ASTM E 96:  0.141 grains per hour per square foot (0.098 grams per hour per square meter).
  104. NOTE ** Retain one of the following two sub-paragraphs to specify batt thickness.
  105.         6.    Thickness:  4 inches (101 mm), nominal, having nominal R-value 13 (2.28 metric equivalent) in accordance with ASTM C 236.
  106.         7.    Thickness:  6 inches (152 mm), nominal, having nominal R-value 19 (3.34 metric equivalent) in accordance with ASTM C 236.
  107. NOTE ** Retain one of the following two sub-paragraphs to specify batt width.
  108.         8.    Batt width: Nominal 48 inches (1.2 m).
  109.         9.    Batt width: Nominal 72 inches (1.8 m).
  110.         10.    Roll length:  150 feet ( 45.7 m).
  111.  
  112.     B.    Thermal Blocking:  Extruded polystyrene sheet conforming to ASTM C 578; thickness 1 inch (25 mm) nominal.
  113.  
  114.  
  115. PART 3    EXECUTION
  116.  
  117. 3.1    INSTALLATION
  118.  
  119.     A.    Install insulation in accordance with manufacturer's instructions.
  120.  
  121.     B.    Field-forming of pockets in insulation is not permitted.
  122.  
  123.     C.    Install insulation, parallel to roof slope and perpendicular to purlins, progressing from eave to ridge.
  124. NOTE ** Delete the following paragraph if project conditions require left to right installation, or left to right installation in addition to right to left installation.  "Opposite side" ConSealTab rolls will be required for left to right installations.
  125.  
  126.     D.    Install insulation rows beginning from right to left.
  127.  
  128.     E.    Roll out insulation using pipe or other device inserted through cardboard core of insulation roll as spindle; ensure that exposed tab trails direction of progress.
  129. NOTE ** Delete the following paragraph if thermal blocking not required.
  130.  
  131.     F.    Place thermal blocks at end-to-end butt joints, covering joint a minimum of 4 inches (101 mm) each side of joint.
  132.  
  133.     G.    Adjust each row of insulation to lay flat across purlins.
  134.  
  135.     H.    As each successive row of insulation is placed, snug roll against previous row, pulling up exposed tab between the two rows.
  136.  
  137.     I.    Beginning at end of row, pull back long edge of batt on previous row, allowing exposed tab to fall into place; smooth exposed tab down against facing from previous row, ensuring that tab lays flat, then drop batt from previous row back into place, ensuring that batts are snug against each other.
  138.  
  139. 3.2    PROTECTION OF INSTALLED PRODUCTS
  140.  
  141.     A.    Do not allow exposure of installed insulation to moisture; install only the quantity of insulation in a single period of construction activity that will be covered by roofing in that period.